What the scale describes
AWG, American Wire Gauge, numbers conductor sizes in steps where every three gauges roughly doubles the cross-section. 10 AWG is a typical solar extension cable; 4 AWG and 2 AWG are battery and inverter cables; 1/0 (one-aught) and larger serve big banks. Metric listings give the cross-section in mm² instead: 4 AWG is about 21 mm², 2 AWG about 34 mm², 10 AWG about 5.3 mm².
Why 12 V needs thick cable
Power is volts times amps, so at 12 V the current is ten times what it is at 120 V for the same load. The inverters on this site show the scale: about 90 A for a 1,000 W unit, about 180 A for LANDERPOW’s 2,000 W and over 220 A for JARXIOKE’s 2,500 W. That is why Renogy supplies two 3 ft 4 AWG cables with its P2 1,000 W, and LANDERPOW two 2 ft 2 AWG cables with its 2,000 W unit. ALLWEI’s 6 AWG cables are thinner for the same 1,000 W.
Length is part of the size
Voltage drop grows with length. A cable adequate over 3 ft may not be over 10 ft. For DC-DC chargers running from the front of a van to the back, the run can exceed 15 ft each way, and the gauge must account for the round trip.
Where the convention stops
AWG tells you the copper, not the insulation rating, the strand count or the temperature rating, all of which affect ampacity. Fine-stranded cable is easier to route and crimps differently. The cable maker’s ampacity table, not a rule of thumb, is the reference.
Fuses follow the cable
A fuse protects the cable, so it is chosen for the cable’s ampacity and placed close to the battery. A 1,000 W inverter on 4 AWG typically sits behind a fuse sized for that cable, not for the inverter’s peak.
What people ask before they order
Is 4 AWG the same as 25 mm²?
Close: 4 AWG is about 21 mm². Conversions are approximate because the two scales do not share steps.
How do I choose a gauge?
From the current and the round-trip length of the run, using the cable maker’s ampacity table and an acceptable voltage drop, typically 3% or less at 12 V.
Why does voltage drop matter more at 12 V?
A 0.5 V loss is 4% of 12 V but under 0.5% of 120 V. The same cable that is fine for household circuits starves a 12 V inverter.
Last reviewed November 2, 2026